|
Ventilation
controls are those controls intended to minimize employee exposure to
hazardous chemicals by removing air contaminants from the work site.
There are three main types of ventilation controls:
- General (Dilution) Exhaust - a room or building-wide system
which brings in air from outside and ventilates within. Laboratory
air must be continually replaced, preventing the increase of air
concentration of toxic substances during the work day. General
exhaust systems are not recommended for the use of most hazardous
chemicals.
- Local Exhaust - a ventilated, enclosed work space intended to
capture, contain and exhaust harmful or dangerous fumes, vapors
and particulate matter generated by procedures conducted with
hazardous chemicals.
- Ductless, or Portable Fume Hoods – an enclosed work space
which employs filtration media, may be an option to conventional
local exhaust hoods.
To determine ventilation requirements, assess the MSDS. Some MSDS
terminology, as listed below, may indicate a need for special
ventilation considerations beyond general exhaust:
- use with adequate ventilation
- avoid vapor inhalation
- use in a fume hood
- provide local exhaust ventilation
Local exhaust
ventilation is the one of the best engineering methods available to
reduce the health hazard risk associated with the use of hazardous
chemicals in the laboratory. Laboratory fume hoods are the most common
local exhaust ventilation devices found in the laboratory. Fume hoods
are used to prevent hazardous, offensive, or flammable gases and vapors
from mixing with the general room air. A hood, especially with the sash
down, acts as a physical barrier between the laboratory workers and
chemical reactions. The hood can also contain accidental spills of
chemicals
|
|
Inspection
of Local Ventilation Systems
Laboratory fume hoods
should be inspected annually. Hoods are passed or failed for use based
on the following criteria:
-
The face velocity
of air being drawn into the hood at maximum sash height is
measured quantitatively in feet per minute (fpm) by a
thermoAnemometer (a hot wire). One measurement is taken per square
foot of face space and averaged. Hoods must have an average face
velocity of 60-150 fpm, depending on their design, with 100 fpm
being the ideal average face velocity.
-
The turbulence of
the air is measured qualitatively by releasing smoke from a smoke
tube. The smoke must be captured by the hood, with a minimum of
turbulence.
|
|
Proper
Use of Local Ventilation Systems
No large, open-face hood
with a low face velocity can provide worker protection against all
events that may occur in the hood. The hood may not adequately protect
the worker from volatile or airborne contaminants with a low exposure
limit (part per billion range). For typical exposures, a well designed
hood in a properly ventilated room can provide adequate protection.
However, certain work practices are necessary in order for the hood to
perform adequately. The following work practices are generally required;
however, more stringent practices may be necessary in some
circumstances. |
Recommended
Work Practices for Laboratory Fume Hoods
-
Conduct all operations
that may generate irritating and/or hazardous air contaminants
inside a hood.
-
Keep all apparatus and
chemicals at least 6 inches back from the face of the hood.
-
Do not lean into the
hood or put your head in the hood when contaminants are being
generated.
-
Do not use the hood as
a waste disposal method (i.e., volatilize chemicals).
-
Do not store chemicals
or apparatus in the hood. Store hazardous chemicals in an approved
safety cabinet.
-
Maintain the hood sash
closed as much as possible.
-
Keep the slots in the
hood baffle free of obstruction by apparatus or containers.
-
Use equipment with legs
or otherwise raise it off the work surface to allow even airflow
under equipment as well as around and over it.
-
Minimize sources of
turbulence at the hood face (e.g., foot traffic, equipment, fans,
moving arms in and out of the hood).
-
Keep laboratory doors
closed whenever possible.
-
Do not remove hood sash
or panels except when necessary for apparatus set-up. Replace sash
or panels before operating hood.
-
Do not place electrical
receptacles or other ignition sources inside the hood when
flammable liquids or gases are present. No permanent electrical
receptacles are permitted in the hood.
-
Use an appropriate
barricade or shield, if there is the possibility of explosion or
eruption.
-
Periodically check the
air flow in the hood using a continuous monitoring device or
another source of visible air flow indicator. If air flow has
changed, contact Supervision.
-
Unlabeled chemicals,
unused equipment, materials, etc., are subject to removal and/or
disposal.
|