| Types of Equipment | Lockout/Tagout Procedures |
| Air Cooled Condensors |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect and lockout/tagout. 3. Valve off refrigerant and lockout/tagout. 4. Verify lockout/tagouts. 5. If refrigerant is to be removed, then follow proper reclaim procedures. 6. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Air Dryer Cooler for Compressors |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect and lockout/tagout. 3. Close compressed air tank valve and lockout/tagout. 4. Bleed off air in unit. 5. Verify lockout/tagouts. 6. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Condensate Receivers |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect to pumps and switches and lockout/tagout. 3. If hydraulic, then valve off fluid, bleed pressure and lockout/tagout. 4. If pneumatic, then valve off air supply, bleed air and lockout/tagout. 5. Valve off condensate supply and return and lockout//tagout. 6. Verify lockout/tagouts. 7. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Control Valves |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. If pneumatic, then valve off air supply, bleed air and lockout/tagout. 3. If electric, then open electrical disconnect and lockout/tagout. 4. Verify lockout/tagouts. 5. When work is complete, notify area personnel and remove lockout/tagout.
|
| Cooling Towers |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect to pumps, automatic fill device, and control devices and lockout/tagouts. 3. Valve off condensate supply line and return lines and lockout/tagout. 4. Valve off supply water to tower and lockout/tagout. 5. If backflow preventor is used on supply, then valve off and lockout/tagout. 6. Verify lockout/tagout. 7. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Electric Air Compressors |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect and lockout/tagout. 3. Close compressed air tank valve and lockout/tagout. 4. Open relief valve to tank and bleed off air in tank. 5. If dual piston, follow manufacturers procedures if working on pistons. 6. Verify lockout/tagouts. 7. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Elevators |
1. Notify affected facility personnel of lockout/tagout, as appropriate. 2. If a shutdown is necessary, then open electric disconnect and lockout/tagout. 3. If elevator is hydraulic, then open electrical disconnect to hydraulic pump and lockout/tagout. 4. Verify lockout/tagouts. 5. When work is complete, notify are personnel and remove lockout/tagouts.
|
| Emergency Generators |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect to switching relay and lockout/tagout. 3. Open electric disconnect to electric output and lockout/tagout.
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect and lockout/tagout. 3. Valve off forced water or chilled water and lockout/tagout. 4. If working on fan coil control valve, then follow manufacturers procedures for many are spring loaded. 5. Verify lockout/tagouts. 6. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Fume Exhaust Hood |
1. Notify laboratory manager that exhaust hood will be worked on. 2. Laboratory manager must ensure all materials are removed from area. 3. Locate exhaust fan motor control. 4. Lockout/tagout electrical disconnect. 5. Tagout exhaust hood and inform laboratory personnel of repairs being made. 6. If plumbing work is to be performed, then valve off water supply and lockout/tagout. 7. Verify lockout/tagouts. 8. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Heat Pumps |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect to heat pump and condensor and lockout/tagout. 3. Valve off refrigerant and lockout/tagout. 4. Verify lockout/tagouts. 5. If refrigerant is to be removed, then follow proper reclaim procedures. 6. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Heating Boilers |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Valve off fuel source (e.g., gas, oil) and lockout/tagout. 3. Open all electric disconnects to boiler, controls, pumps, circulators and receivers and lockout/tagout. 4. If forced hot water boiler, then valve off backflow preventor water supply and lockout/tagout (drain boiler of water). 5. If steam boiler, then valve off backflow preventer water supply and lockout/tagout (displace steam pressure via safety relief valve). 6. Verify lockout/tagouts. 7. When work is complete, notify area personnel and remove lockout/tagouts.
|
| Hot Water Heaters |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Valve off fuel source (e.g., gas, oil) and lockout/tagout.
6. Verify lockout/tagouts. 7. When work is complete, notify area personnel and remove lockout/tagouts.
|
| HVAC Systems |
1. Notify affected personnel of lockout/tagout, as appropriate. 2. Open electric disconnect to unit and lockout/tagout. 3. Valve off forced water, chilled water or steam and lockout/tagout. 4. If unit has energy recovery coil, valve off supply and return lines and lockout/tagout. 5. Open electric disconnect to pumps and lockout/tagout. 6. If unit has electrostatis filter, then open electric disconnect and lockout/tagout. 7. If unit has electric re-heat, then open electric disconnect and lockout/tagout. 8. Verify lockout/tagouts. 9. When work is complete, notify area personnel and remove lockout/tagouts.
|